Xtremevan consumer unit

Discussion in 'Mech Tech' started by ginger ninja, Dec 20, 2020.

  1. Marvellous

    Sent from my SM-G960F using Tapatalk
     
    PanZer likes this.
  2. Can you give us the exact product details please?
    I'm going for a socket only set up and want as small physical size as possible (but maximum safety protection obviously)
     
    Lasty likes this.
  3. You want a double pole 16A type B RCBO, summut like this. I have no idea who Cudis are.

    https://www.cef.co.uk/catalogue/products/921320-16a-dp-2-module-6ka-type-b-30ma-rcbo

    This is the box I put mine in. Very neat. Just a plastic DIN rail inside, no busbars, so you'll need to use some terminal block to connect up the earth.

    https://www.screwfix.com/p/wylex-ese2-ip40-2-module-unpopulated-din-enclosure/32311
     
    paulcalf likes this.
  4. 77 Westy

    77 Westy Supporter

    CPN Cudis is supplier of electrical circuit protection components, founded in 2004 with headquarters in Bury, Greater Manchester. All their products are manufactured in China and sold under the CPN brand name. :thumbsup:
     
    Betty the Bay likes this.
  5. Protect you earth leakage long time :thumbsup:
     
    Lasty, Norris, matty and 3 others like this.
  6. Betty the Bay

    Betty the Bay Supporter

    Lancastrian and Chinese.....a recipe for disaster.
     
    Meltman, 77 Westy and snotty like this.
  7. I regret installing their Covid MCBs :(
     
    Meltman, 77 Westy and Betty the Bay like this.
  8. Thanks very much for the info.

    Looks like CEF even have a branch less than a mile from me!
     
  9. Don’t forget to wear your trackie bottoms when you go in there.

    If there’s a plumbers merchants next door, why not pick up a copy of the latest Victorias Secret catalogue :thumbsup:
     
    Meltman and paulcalf like this.
  10. It can't be as bad as toolstation, which i had to go in last week!
     
    snotty likes this.
  11. They’re more hygenic in Screwfix.
     
    Meltman and paulcalf like this.
  12. matty

    matty Supporter

    PanZer, paulcalf and snotty like this.
  13. ginger ninja

    ginger ninja Supporter

    Quick question on all this. In my consumer unit it asks me to wire the Earth terminal to a suitable earthing terminal on the chassis. But with rubber tyres all round this isn’t going to help if the bodywork went accidentally live (which is one of the main reasons for all the safety gubbins). As it will be totally insulated from ground.
    In my head the Earth is connected to mains input cable which would trip out the mains supply from the camp site. Am I being a buffoon? I’m going to do it anyway but was just wondering.
     
  14. If you had a live chassis, you’d get belt as soon as you stepped out of the van (as would anyone who touched the bodywork). The whole van would be one big live terminal.
     
  15. ginger ninja

    ginger ninja Supporter

    Yes I know. That wasn’t my question. I’m asking how wiring the Earth to the chassis helps when there are four rubber tires that insulate the van from ground and therefore would not help if the chassis went live. As I say I’m going to do it any way, was just wondering for my own understanding. If the Earth terminal was wired to the Earth in the mains input cable that should do the trick no?
     
  16. Because an electrical fault (say your metal kettle in the van went live) needs to return a large current via earth in order to trip the breaker. The bodywork of the van needs to be connected to the incoming earth connection from the hookup.

    The RCD is the bit that protects you. If it detects a small amount of current that’s gone missing (likely through you), it will trip its breaker part and disconnect the supply. The RCD doesn’t rely on an earth connection.
     
    Last edited: Jan 14, 2021
    ginger ninja likes this.
  17. ginger ninja

    ginger ninja Supporter

    Got it!
    That makes complete sense thank you @snotty
    P.
     
    zv6883 and snotty like this.
  18. Think of it as two parts: the MCB bit trips on a large current to protect the wiring (but not you), the RCD bit trips on a much smaller current (a few tens of milliamps) to protect you, hence the need for both.
     
    ginger ninja and PanZer like this.
  19. ginger ninja

    ginger ninja Supporter

    Cheers. I’m glad I’ asked. :thumbsup:
     
    snotty likes this.
  20. ginger ninja

    ginger ninja Supporter

    Well after 3 years of asking questions, 3 different threads, and squirrelling away bits by buying them gradually so as to avoid suspicion from missus. I managed to fit it all bit by bit over the 2nd lockdown. Out with the old Dr Who transformer and 110v sockets and inlet socket and in with the new. I wanted to keep the original inlet flap so a lot of thought went into it.
    Thank you to @matty @Valveandy @snotty @theBusmonkey @mikedjames and so many others !!

    it all works superbly and the buzz socket tester agrees.

    Thank you again everyone.
     